Heat stress and cooling systems for dairy cows
Automated Control of Shower Cooling

For example, in the LO-Range setting, the user could  program the C-400 Controller to commence cooling when temperatures reach  75oF (Actuation Temperature). The controller could activate  up to 4 electric valves in sequence, to permit showering for a 2-minute  period of time (Shower Time) during a 20-minute cycle. Only one electric  valve would be activated at any one time. Thus, with 4 valves, during  the 20-minute cycle time, there would be a total of 8 minutes of  showering, (2 minutes from each of the 4 valves) followed by 12 minutes  with no showering (Interval Time). At the end of this cycle, the  controller checks the temperature again, and if the temperature is above  the programmed level of 75oF, the cycle will start all over again.
After setting the LO-Range program, the user could set the HI-Range program to begin at temperatures of 85oF  or above. In this HI-Range setting, the unit could be programmed to  activate each of the electric valves for 1-1/2 minutes of showering  during a 10-minute cycle time. This would amount to a total of 6 minutes  of showering, (1-1/2 minutes from each of the 4 valves) followed by 4  minutes with no showering. When the temperature drops back below the  setting of 85oF, the controller will switch back to the LO-Range program.
  
There  should be a continuous flow of air over the backs of the cattle any  time the cooling system is in operation. This causes the water to be  evaporated, which takes the heat away from the cattle in the process.  Fans would be controlled separately from the cooling system, and could  be set to operate continuously above a temperature of 70oF.
   Programming of the C-400 Controller is easy to do. Time and temperature  settings in both LO-Range and HI-Range are easily viewed and adjusted  as desired. The shower times and interval times can be set anywhere  within the range of 0 - 99 minutes, while the actuation temperature can  be set anywhere between 40o - 99oF in either the  LO or HI-Range settings. You can also select the number of electric  solenoid valves that are to be operated. Once the settings are entered,  they are saved automatically, and will not be lost if the electrical  power is interrupted.
             It does not have to be 110oF for heat stress to occur in dairy cows!
Studies have found that at temperatures as low as 79oF,  dairy cows will begin to cut feed intake and lose body weight. Milk  production falls. Reproductive performance, health, and lactational  performance are affected. Heat stress will continue to affect  performance even in the cooler months ahead. High yielding cows are most  susceptible to heat stress. All of this quickly impacts your pocket  book!
The degree of heat stress suffered by the cow will depend  on the combination of environmental conditions - air temperature,  relative humidity, air movement, and radiation from the sun. Dairymen  use shades, fans, and ample fresh drinking water to help herds beat the  heat; but often shade and ventilation are just not enough. In southern  states, where heat and humidity are more severe, dairymen have also used  sprinklers to provide added cooling effects.
Research has  shown that intermittent showering in combination with shade and forced  air movement is a very effective method of cooling diary cows, thereby  reducing the production losses experienced during hot humid weather  conditions. By using a high capacity, coarse droplet shower nozzle,  enough water can be applied to fully wet the cows to the hide. The water  is then allowed to evaporate, which pulls heat from the animal, just  like sweating. Increased air movement across the wet hide provided by  fans, makes this system most efficient.
Disadvantages of Misting and Fogging
   Mist and fogging nozzles have been used to cool dairy cows, and have  proven advantageous in dry climates. They work by cooling the air around  the cows. The disadvantage is that the mist can be easily blown away  under windy conditions, or when used with fans. If a mist or fog builds  up on the cow’s hair coat, it can trap a layer of air between the skin  and the water, which holds in body heat. Respiratory problems can also  arise if proper ventilation is not provided. In addition mist and  fogging nozzles usually must be operated at high pressures and require  regular maintenance, especially when poor water quality conditions  exist.
  In comparison, shower nozzles produce coarse droplet  spray which penetrates the hair coat and wets the cow’s skin. To avoid  formation of a mist the shower nozzles operate at reduced water pressure  of 10-15psi.
Typical Installation of a Shower Cooling System

  Normal  recommendations are to shower the animals for a short period of time,  0.5 - 3 minutes, to wet the hide. After the shower shuts off, the water  is evaporated from the cattle by the air from fans blowing across their  backs for 5-15 minutes, before repeating the shower cycle.
  The  most common locations for installing a shower cooling system are in the  holding pen area, where cows are crowded together tightly, and in the  feed bunk area. An air velocity of 400-600 ft/min over the cows' backs  is recommended. A 36-inch fan providing 11,000 cfm will move air  effectively for 20-30 feet, and a 48-inch fan will move air up to 40  feet. Fans should be placed as low as possible, while still allowing  clearance for cows and equipment. Nozzles should be mounted just below  the fans.
  We offer all the components you need to economically  set up an intermittent showering system in your facility. The Edstrom  C-400 Controller permits you to control up to 4 electric water valves  activated in sequence. This electronic controller has a  user-programmable thermostat and time settings.
  We offer a  selection of Shower Nozzles. In addition, an economical 24VAC, 3/4-inch  electric valve and filter are offered for installing in your water line.  You only need to provide the water distribution pipelines, electrical  connections, and the ventilation fans.
  The Edstrom Controllers  can be ordered with either a 24VAC/110VAC transformer, or a 24VAC/220VAC  transformer. This allows you to choose the system that will best fit  your operation.
Typical Set Up of a Cooling System
   1. First determine where you want to locate the shower nozzles. They  should not be installed where they will spray into the feed bunk or a  stall area. Common locations are at the feed bunk and in the holding pen  areas.
                    
   In the holding pen area, full-circle (3600) nozzles are recommended,  and should be located to obtain 100% coverage of the area to be sprayed  at a height of about 4-1/2 ft. above the floor. At the feed bunk,  1/3-circle (1200) nozzles can be mounted along the top of the bunk head  gate and directed to spray out over the backs of the cows
  2.  Next, determine the plumbing arrangement. This will depend on the  quantity and type of nozzles being installed, as well as the water flow  capacity of your facility. Multiply the number of nozzles by the  nozzles' rated capacity to obtain the total water flow-rate required for  the facility. The electric valve-filter-pressure reducer used to  control the flow to the nozzles has the capacity to handle up to 15 gpm.  If the total flow-rate required for the facility exceeds this capacity,  or if the farm water supply is not capable of supplying water at this  rate, the nozzle lines need to be divided into sections, or "zones",  each supplied by a separate electric valve-filter-pressure reducer. (The  C-400 Controller will activate the Electric Valves in sequence; they  will not all come on simultaneously.)
  When installing the  system, locate the electric valve-filter-pressure reducer centrally in  each line of nozzles to balance the water pressure to the far end of the  lines.
  3. The C-400 Controller should be located where it will  be easy for the operator to view and make program adjustments. The unit  is powered by a 24VAC transformer (included with the controller), which  must be plugged into an 110VAC outlet. An optional 220VAC transformer  is also available. Electric wiring connects the controller to each  electric valve. This is a low-voltage 24VAC circuit. (A 50 ft. roll of  low-voltage wire is included with each electric valve kit.)






















